VOLTAGE MEASUREMENT SPEED AS A PARAMETER FOR ENSURING SELECTIVE OPERATION OF THE BACKUP STAGE OF REMOTE PROTECTION TsZA FKS – 27,5
Keywords:
distance protection, catenary feeder, the contact network feeders, MATLAB SIMULINK, voltage change rate measurementsAbstract
The article discusses the problem of false activation of directional distance protection of contact network feeders during the passage of heavy freight trains of increased mass. To solve this problem, it is proposed to improve the protection operation algorithm using identification of the parameter for measuring the rate of voltage change. The article presents mathematical and simulation modeling using the MATLAB SIMULINK program and an algorithm for the operation of directional distance protection of contact network feeders to test the operation of the protection and increase its reliability when passing heavy trains.
References
СТО РЖД 07.021.1-2019. "Защита систем электроснабжения железной дороги от коротких замыканий и перегрузки. Часть 1. Общие принципы и правила построения защит, блокировок и автоматики в системах электроснабжения". Распоряжение ОАО "РЖД" от 15.01.2020 N 37/р. – 34 c.
Устройство третьей ступени дистанционной защиты фидеров контактной сети. / Трифонов Р. С., Филиппов С. А., Яковлев Д. А., Соловьёва О. А. // № RU 201026 U1 дата регистрации 05.06.2020 г., опубликовано 24.11.2020 г. Бюл. №33
Руководство по эксплуатации 1СР.251.249 - 02 РЭ. Устройство цифровой защиты и автоматики фидера контактной сети ЦЗА-27,5-ФКС. 53 с.
Трифонов Р. С. Повышение селективности резервной ступени дистанционной защиты фидеров контактной сети на основе адаптивной идентификации Омск 2016, 187 с.
Руководящие указания по релейной защите систем тягового электроснабжения. Департамент электрификации и электроснабжения ОАО «Российские железные дороги». – М. «Трансиздат», 2005 г. – 216 с.